Construction
Manufactured from 0.5mm 430 grade stainless steel in diameters
from 100mm - 300mm as standard. Larger sizes are available.
All pipe lengths are double-lockseamed on longitudinal seams
to ensure a leak proof installation.
Typical Applications
Can be used on gas and oil fired space heaters and boilers,
combustion air ducting, fan dilution systems, air conditioning
and ventilating ducts, steam venting in laundries etc, and
flue pipe connections for some domestic and commercial gas
appliances. 430 grade stainless steel can also be used on
many fume extract ducts but check suitability with us as another
grade of stainless steel may have to be specified.
Installation
Sections can be joined together using self tap screws or
pop rivets. Alternatively securing bands can be used. All
male (crimped) ends should point downwards to eliminate leakage
of condensate.
Roof Penetration
Change over sections are available which have both ends crimped
to prevent rain entering joints above roof level. These sections
are fitted where the flue run passes through the roof.
Flashing plates are available in lead, aluminium or stainless
steel. The pitch of roof must be specified on lead flashings
but standard adjustable flashings are suitable for roofs from
0-30 pitch. Storm collars or cravats should be fixed to fluepipe
immediately above flashing plate and should be sealed to fluepipe
with silicon or similar non setting sealant.
Terminals
Use standard cowls on oil-fired appliances and double-inverted
cowls on induced draught systems to reduce back pressure in
flue. Gas terminals should only be used on gas appliances.
Universal Terminals are suitable for either Oil or Gas.
Other terminals can be manufactured where downdraught is
present. |
|
Support
Standard wall brackets are supplied with 305mm long stems
made from 25 x 25 x 3mm mild steel angle. These can be cut
to length on site if required. Support should always be given
to the flue immediately above any offset.
Ceiling Plates
Are available to fasten to underside of roof to neaten the
appearance where flue passes through.
Special Items
Non-standard items such as modular tees for multi-boiler
installations, adaptors or special angled elbows, etc., can
be supplied on receipt of a dimensioned drawing or sketch.
Assembly
Push starter into either appliance or single wall pipe and
secure. Insert the crimped end of std pipe length into inner
sleeve of starter. Another std pipe of 50mm greater diameter
is then placed around the inner pipe and inserted into the
outer sleeve of starter and secured. At the end of each section
a connector is used to keep the inner and outer length of
pipe concentric. Continue assembling in this manner for as
long as required. At the termination of the twinwall section
a terminator is used to close gap between inner and outer
sections.
Other Products
Single wall stainless steel can be supplied in 304 and 316
grade for solid fuel appliances and where greater corrosion
resistance is required. Details supplied on request. |